Main Features
1. AC Inverter, Optional With built in MPPT SCC(Solar Charge Controller)
2. Able to Charge Battery by using solar power without consuming Power from AC mains
3. Wide AC input voltage range which supports both AC mains and generator
4. High efficiency results in energy saving
5. AC restart when AC is recovering
6. Strong charging capability which gives flexibility on battery configuration
7. Selectable Solar or AC priority function
8. Adjustable charge current
Specification
Model | PSC Plus3K-24 | PSC Plus5K-48 | |
AC | Nominal Power | 3KVA/2400W | 5KVA/4200W |
Input Voltage Waveform | Sinusoidal (utility or generator) | ||
Nominal input Voltage | 230VAC | ||
Low Line Disconnect | 170Vac±4%(Normal) or 90Vac±4% (Wide&Gen) | 175Vac±4%(Normal) or 125Vac±4%(Wide&Gen) | |
High Line Disconnect | 280Vac±4%(Normal) or 280Vac±4%(Wide&Gen) | 280Vac±4%(Normal) or 280Vac±4%(Wide&Gen) | |
Max AC input Voltage | Max:300VAC | ||
Frequency | 50Hz/60Hz(Auto detection) | ||
AC | Output Voltage Waveform | Sine wave | |
Power Factor | 0.8 | 0.84 | |
Bypass Breaker Size | 30A | 40A | |
Nominal Output Frequency (Hz) | 50Hz / 60Hz ± 1Hz | ||
Capable of starting electric motor | 1.5HP | 2.5HP | |
Full load efficiency | 90% | ||
Solar | Charger mode | MPPT | |
Maximun PV Array Power | 960W | 2800W | |
Rated Charge Current | 40A | 60A | |
PV Low Voltage Disconnect | 25VDC±0.6VDC | 50VDC±1.2VDC | |
PV High Voltage disconnect | 75VDC±0.6VDC | 150VDC±1.2VDC | |
Efficiency | ≥98% | ||
AC | Nominal Charger Current | 20A @170Vac~280Vac; 10A @90Vac~170Vac | 25A @180Vac~280Vac; 20A @125Vac~180Vac |
Over charge Protection | 30VDC±0.6VDC | 60VDC±1.2VDC | |
Floating Charge Voltage | 27.4VDC±0.6VDC | 54.8VDC | |
Battery | Nominal DC input Voltage | 24VDC | 48VDC |
Low Battery Alarm | 21VDC±0.6VDC | 42VDC±1.2VDC | |
High DC input Alarm & Fault | 29VDC±0.6VDC | 58VDC±1.2VDC | |
Transfer Time | Normal range : 10ms (typical) 15ms (max) | ||
System | Over-Load Protection | 110%the output,load≥150%,beeps 0.5s every 1s,and Fault after 5s | |
Output Short Circuit Protection | Current limit (Fault after 4 cycles max) | ||
Surge Rating | 1:2(VA) | ||
Protections | Low battery, over charging, over load, over temp | ||
General | Operating Temperature Range | 0ºC to 40ºC | |
Storage Temperature | -15ºC~60ºC | ||
Operation Humidity | 5% to 95%(non-condensing) | ||
Audible Noise | 60dB max | ||
cooling | Forced air,variable speed fan | ||
Dimension(L*W*H) | 326*268*88.8mm | 456*356.8*118mm | |
Net Weight(kg) | 5.6 | 11.1 |
Photos




#########################################################################################
Specically Recommand: 300-12000W Solar Inverter Hybrid Power Inverter

Any inquiry, pls kindly contact Sunny..